TSS

GASCO, 1 solar system, 50,085Wp

United Arab Emirates | TSS was contracted by Galfar Engineering & Contracting to build 1 system

For end user GASCO TSS was contracted by Galfar Engineering & Contracting to build 1 system.
Application: Remote Terminal Unit (RTU), telecom and metering
System capacity: 5,194 Ah/d @ 24Vdc

Design features:

Solar array of 50,085 Wp – Battery bank of 42,768 Ah @ C120 @ 24Vdc

GASCO project TSS

ADCO, 4 solar systems, 28,350Wp

United Arab Emirates | 4 systems for contractor Dodsal Engineering & Construction

For contractor Dodsal Engineering & Construction 4 systems were placed. The end user of these systems is ADCO.
Application: Block Valve Station (BVS)
System capacity: 3,322 Ah/day @ 24Vdc (not all systems are of the same capacity)

Design features:

Solar array of 28,350 Wp – Battery bank of 34,240 Ah @ C120 @ 24Vdc

Adco project UAE

Sonatrach, 25 solar systems, 30,600Wp

Algeria | TSS built 25 systems for contractor Samsung Engineering

TSS built 25 systems for contractor Samsung Engineering. The end user is GTIM.

Application: Remote Terminal Unit (RTU), Well Head Control Panel (WHCP) and metering
System capacity: 2,400 Ah/day @ 24Vdc (not all systems are of the same capacity)

Design features:

Solar array of 30,600 Wp – Battery bank of 16,935 Ah @ C72 @ 24Vdc

Algeria project TSS

L&T, 5 ATEX/IECEx solar systems, 15,900Wp

United Arab Emirates | ATEX/IECEx zone 1 Solar Power systems for contractor L&T

5 pcs. ATEX/IECEx zone 1 Solar Power systems for contractor L&T. Installed in ADNOC offshore Umm Lulu & Nasr fields.
Application: Full power supply of 5 unmanned platforms
System capacity: Systems ranging from 1100 Ah/day @ 24Vdc up to 2200 Ah/day @ 24Vdc
Design features: Solar arrays ranging from 15,900 Wp up to 30,700Wp Battery banks ranging from 24,255 Ah @ C180 @ 24Vdc up to 48,510 Ah @ C180 @ 24Vdc
United Arab Emirates project TSS

BP, 1 solar system, 19,520Wp

Oman | Solar Power Systems for passive cooled shelter supplier Celantel

1 pc. Solar Power systems for Passive Cooled Shelter supplier Celantel. Installed for the BP Oman Khazzan Gas Project-P2-SXW.
Application: RTU, Telecom, Passive Cooled Shelter lights. Designed in a dual (2×50%) system setup
System capacity: Systems ranging from 2217 Ah/day @ 24Vdc

Design features:

Solar array 19.520 Wp. Battery bank 3,672 Ah @ C120

Oman project TSS

Shell 7 ATEX/IECEx solar systems, 6,120Wp

UK/the Netherlands | Supply and maintenance hybrid solar power systems for Shell/NAM

Supply and (remote) maintenance of 7 pcs. ATEX Solar (zone 1)-Wind (zone 2) hybrid solar power systems for Shell UK/NAM. Installed on North Sea gas platforms.

Application:

Full and only power supply of 7 unmanned platforms. Designed in a dual (2×50%) system setup

System capacity: Systems ranging from 1200 Ah/day @ 24Vdc up to 1400 Ah/day @ 24Vdc

Design features:

Solar arrays ranging from 6,120 Wp up to 6,8400Wp Battery banks ranging from 7,728 Ah @ C120 @ 24Vdc up to 11,592 Ah @ C120 @ 24Vdc

UK Netherlands project TSS

ADNOC, 151 solar systems, 5,580-12,400Wp

United Arab Emirates | Solar Power Systems for contractor Tecnicas Reunidas

151 pcs. Solar Power Systems for contractor Tecnicas Reunidas. Installed for the Adnoc Onshore Bu Hasa integrated field development project.

Application:

RTU, Telecom, WHCP, Chemical Injection package, corrosion inhibitor skid, instrumentation, valves

System capacity: Systems ranging from 578 Ah/day @ 24Vdc up to 1305 Ah/day @ 24Vdc

Design features:

Solar arrays ranging from 5,580 Wp up to 12,400Wp. Battery banks ranging from 3,764 Ah @ C72 @ 24Vdc up to 8,860 Ah @ C72 @ 24Vdc

UAE project TSS

KOC, 15 solar systems, 7,930-13,420Wp

Kuwait | Solar Power Systems for contractor Larsen & Toubro Hydrocarbon Engineering Ltd.

15 pcs. Solar Power Systems for contractor Larsen & Toubro Hydrocarbon Engineering Ltd. Installed for the KOC new 48” crude transit line from North Kuwait to CMM project.

Application:

RTU, Telecom, Scada, security system, outdoor camera, lighting

System capacity:

Systems ranging from 921 Ah/day @ 24Vdc up to 1645 Ah/day @ 24Vdc

Design features:

Solar arrays ranging from 7,930 Wp up to 13,420 Wp. Battery banks
ranging from 5,184 Ah @ C72 @ 24Vdc up to 9,828 Ah @ C72 @ 24Vdc

KUWAIT project TSS